全部作者:赵勇 罗万象
文献出处:《暖通空调》 年份:2000 期数:4
论文摘要:
【英文篇名】 Trouble shooting and adjusting for the air conditioning system in an office building 【作者中文名】 赵勇; 罗万象; 【作者英文名】 By Zhao Yong and Luo Wanxiang; 【作者单位】 中国纺织工业设计院; 【文献出处】 暖通空调, HV 室内空气品质; 风机盘管; 新风; 【英文关键词】 office building; indoor air quality; fan coil unit; fresh air; 【摘要】 针对某办公楼出现的室内相对湿度过高、新风量不足、空气有异味等问题 ,分析了设计资料并进行现场调研 ,采取降低冷水机组供回水温度、调节风机盘管风速、适当关闭风机盘管台数、清洗过滤器等措施 ,基本解决了室内空气品质问题。探讨了该工程空调系统设计中不足之处和运行管理中应注意的问题 【英文摘要】 Aims at the problems such as over high relative humidity, fresh air shortage and poor indoor air quality existed in an office building, analyses the design data and investigates in site. By reducing supply/return water temperatures of the water cooled chiller unit, regulating the air velocity from the fan coil unit, stopping some fan coil units properly and cleaning the air filter, largely solves these problems. Discusses the deficiencies in design and operation of the air conditioning system in the buildin...
关键词:分析 调试 故障 系统 空调 the