我要投稿《暖通空调》论文 - 设备开发

医用无凝水机组的性能优化

上传时间:2010-03-23 浏览量:95
【下载地址】 内容介绍

全部作者:刘 明 唐学波 朱青 

文献出处:《暖通空调》 年份:2010 期数:3

论文摘要:
摘要: 通过改变无凝水机组流程和进风、进水参数,分析盘管冷热量变化及结露情况。研究发现,机组供冷量随着进风温度的升高而增加,随进水温度的升高而减少,进回水温差越小,机组供冷量越大,机组是否结露与进风相对湿度有很大关系。无凝水机组能够在较高供水温度情况下实现较大供冷量,达到设计要求。 关键词 :无凝水机组 干盘管 供冷量 供水温度 Performance optimization of medical unit without condensed water By Liu Ming★, Tang Xuebo, Zhu Qingqing and Shen Jinming Abstract Studies the cooling and heating rate variation and condensation by changing flow pattern and parameters of air and water entering the unit. The experiment results show that cooling capacity of an unit increases as entering air temperature increases, while decreases as entering water temperature increases, and increases as temperature difference of supply and return water decreases. Whether the unit condensation occurs or not is concern with relative humidity of entering air. The unit can provide more cooling quantity than common units under relatively high water supply temperature, satisfying design demands. Keywords unit without condensed water, dry coil, cooling quantity, water supply temperature ★ Shanghai SINKO Air Conditioning Equipment Co., Ltd., Shanghai, China

关键词:无凝水机组 干盘管 供冷量 供水 

下载次数:0 文件大小:0B 文档类型:pdf
下载
相关下载

刘 明 唐学波 朱青 发表的论文

与本论文相关的论文:无凝水机组 干盘管 供冷量 供水 

下载说明

☉尊重知识产权,引用文档中他人文字请注明文章出处!
☉下载压缩包文件时,如要求输入解压密码,统一为 www.51hvac.comwww.e-hvacr.com
☉推荐使用网际快车下载本站软件,使用 WinRAR v3.10 以上版本解压本站软件。
☉如果这个软件总是不能下载的请点击报告错误,谢谢合作!!
☉下载本站资源,如果服务器暂不能下载请过一段时间重试!
☉如果遇到什么问题,请到本站论坛去咨寻,我们将在那里提供更多 、更好的资源!
☉本站提供的一些商业软件是供学习研究之用,如用于商业用途,请购买正版。
☉当您打开下载地址链接后,无法下载文件时,请查看是否在地址栏中提示“为帮助保护您的安全,Internet Explorer 已经阻止从此站点下载文件到您的计算机。单击此处查看选项...”,请鼠标点击该提示选择“下载文件”即可。

------分隔线----------------------------

网友评论

论文下载排行榜

官方微信