全部作者:许钟麟 张益昭 张彦
文献出处:《暖通空调》 年份:2006 期数:12
论文摘要:
【英文篇名】 Analysis of field measured performance parameters of clean operating rooms 【作者中文名】 许钟麟; 张益昭; 张彦国; 刘华; 牛维乐; 冯昕; 崔磊; 曹国庆; 展素萍; 赵力; 梁磊; 姚丹; 刘京; 【作者英文名】 By Xu Zhonglin; Zhang Yizhao; Zhang Yanguo; Liu Hua; Niu Weile; Feng Xin; Cui Lei; Cao Guoqing; Zhan Suping; Zhao Li; Liang Lei; Yao Dan and Liu Jing Institute of Air Conditioning; China Academy of Building Research; Beijing; China; 【作者单位】 中国建筑科学研究院空调所; 【文献出处】 暖通空调, Heating Ventilating 测定; 性能参数; 【英文关键词】 clean operating room; measurement; performance parameter; 【摘要】 对300余个洁净手术室的检验数据进行了统计分析,认为现行规范给出的参数是适宜的,所测得的大部分手术室性能良好;手术室静态沉降菌浓度的检测是必要的;送风量指标可稍作降低。 【英文摘要】 Analyses these performance parameters of more than three hundred clean operating rooms, and considers that the parameters provided in current regulation are suitable. The performance of most clean operating rooms are satisfactory. It is necessary to check the static state concentration of depositing bacteria in clean operating rooms. The design index of supply air rate can be slightly reduced.
关键词:性能 手术 of operating clean
☉尊重知识产权,引用文档中他人文字请注明文章出处!