全部作者:汪训昌
文献出处:《暖通空调》 年份:1999 期数:6
论文摘要:
试论蓄冷空调高峰用电时段冷负荷转移系数——在分割式三段制分时电价下一个值得商榷的认识和政策问题 【英文篇名】 Transfer ratio of cooling load under the current power rate system: a problem for consideration of electricity supply authorities 【作者中文名】 汪训昌; 【作者英文名】 By Wang Xunchang ★; 【作者单位】 中国建筑科学研究院空调所; 【文献出处】 暖通空调, HV 空调; 分割式三段制分时电价; 高峰用电时段冷负荷转移系数; 【英文关键词】 thermal storage; air conditioning; time sharing power tariff; peak time cooling load transfer ratio; 【摘要】 目前大多数电力公司推行的分时电价制度,其高峰时段与办公楼和大型商场空调冷负荷的高峰时段相互错位,如果按当前流行的方法选配制冷机组与蓄冷装置的容量和台数,将导致高峰用电时段的空调冷负荷转移系数极低,业主不能从分时电价政策中获取最大的利益。就此提出了提高补贴幅度的建议和具体方案 【英文摘要】 Considers that the cooling load transfer ratio is made very low when the peak period set in the time division rate system overlaps too less with that of office buildings and large stores in cooling demand and the refrigeration and thermal storage capacity are decided following the current procedure. This must lead the insufficient benefits of the building owner from the incentive price policy. Proposes to lift the subsidy percentage and an option to make more rational division of benefits between power sup...
关键词:转移 系数 时段 高峰 用电 空调