全部作者:李安桂 包 欣 秦二
文献出处:《暖通空调》 年份:2009 期数:12
论文摘要:
摘要: 在试验研究中考察了送风速度和热源发热量对工作区气流组织的影响。试验结果显示,主变室的热源发热量从107 kW增大到178 kW时,气流流场变化不大;送风速度从1.8 m/s增大到3.3 m/s时,气流流场存在较大变化。表明对于有集中热源且采用下送上回气流组织的房间,机械力较热浮升力对气流流场有更大的主导作用。 关键词 :二维粒子图像测速技术 模型试验 送风速度 热源发热量 Thermal scale model experiment of main transformer room ventilation in a hydropower station with two dimensional particle image velocimetry By Li Angui★,Bao Xin,Qin Erwei and Wang Guodong Abstract Investigates the influence of supply air velocity and heat release rate on air distribution in working area. The results show that the heat release rate exerts a little influence on indoor air distribution and working-area air velocity when it increases from 107 kW to 178 kW, and that the supply air velocity has a remarkable effect on the air distribution when it increases from 1.8 m/s to 3.3 m/s. It indicates that mechanical force has larger effect than thermal buoyancy force in a plant with centralized heat source and down-supply and up-return air distribution. Keywords 2DPIV, model test, supply air velocity, heat release rate ★ Xian University of Architecture and Technology, Xian, China
关键词:二维粒子图像测速技术 模型试验
☉尊重知识产权,引用文档中他人文字请注明文章出处!
☉下载压缩包文件时,如要求输入解压密码,统一为 www.51hvac.com 或 www.e-hvacr.com
☉推荐使用网际快车下载本站软件,使用 WinRAR v3.10 以上版本解压本站软件。
☉如果这个软件总是不能下载的请点击报告错误,谢谢合作!!
☉下载本站资源,如果服务器暂不能下载请过一段时间重试!
☉如果遇到什么问题,请到本站论坛去咨寻,我们将在那里提供更多 、更好的资源!
☉本站提供的一些商业软件是供学习研究之用,如用于商业用途,请购买正版。
☉当您打开下载地址链接后,无法下载文件时,请查看是否在地址栏中提示“为帮助保护您的安全,Internet Explorer 已经阻止从此站点下载文件到您的计算机。单击此处查看选项...”,请鼠标点击该提示选择“下载文件”即可。