我要投稿《暖通空调》论文 - 综合文章

二次泵系统中逆向混水现象的分析和解决方案

上传时间:2010-08-27 浏览量:93
【下载地址】 内容介绍

全部作者:姜子炎 韩福桂 王福林 

文献出处:《暖通空调》 年份:2010 期数:8

论文摘要:
摘要 逆向混水是二次泵系统中的常见问题,逆向混水会导致二次侧供水温度上升、末端制冷能力下降、水泵能耗大幅增加等。用仿真软件再现了逆向混水的形成和发展过程,在此基础上探讨了逆向混水产生的条件,以及冷水泵控制和末端调节对逆向混水的影响。指出制冷量不足是逆向混水问题产生的根本原因,并给出解决方案。 关键词 二次泵系统 逆向混水 仿真分析 Analysis and solution for reverse flow in secondary pump system By Jiang Ziyan, Han Fugui and Wang Fulin Abstract Reverse flow is a common issue in secondary pump system, which may lead to the increase of supply water temperature in secondary loop, decrease of the refrigerating capacity of terminal devices, and increase of electricity consumption of pumps. Simulates the forming and developing process of reverse flow by a simulation tool, and discusses the conditions with which reverse flow could occur and the influence of chilled water pumps control and terminal devices regulating. Points out that the inadequate refrigerating effect is the primary cause for reverse flow, and gives solutions. Keywords secondary pump system, reverse flow, simulation

关键词:二次泵系统 逆向混水 仿真分析 

下载次数:8 文件大小:0B 文档类型:pdf
下载
相关下载

姜子炎 韩福桂 王福林 发表的论文

与本论文相关的论文:二次泵系统 逆向混水 仿真分析 

下载说明

☉尊重知识产权,引用文档中他人文字请注明文章出处!
☉下载压缩包文件时,如要求输入解压密码,统一为 www.51hvac.comwww.e-hvacr.com
☉推荐使用网际快车下载本站软件,使用 WinRAR v3.10 以上版本解压本站软件。
☉如果这个软件总是不能下载的请点击报告错误,谢谢合作!!
☉下载本站资源,如果服务器暂不能下载请过一段时间重试!
☉如果遇到什么问题,请到本站论坛去咨寻,我们将在那里提供更多 、更好的资源!
☉本站提供的一些商业软件是供学习研究之用,如用于商业用途,请购买正版。
☉当您打开下载地址链接后,无法下载文件时,请查看是否在地址栏中提示“为帮助保护您的安全,Internet Explorer 已经阻止从此站点下载文件到您的计算机。单击此处查看选项...”,请鼠标点击该提示选择“下载文件”即可。

------分隔线----------------------------

网友评论

论文下载排行榜

官方微信